PHE IN-SHOP RECONDITIONING PROCEDURES

 LogPHE plates and Cross Check factory database to confirm original specs.

 Close-upVisual Inspection of Gaskets and contact points to make sure plates worthreconditioning.

 Pressurewash and rinse Plates & Remove Gaskets and scales.

 ChemicalBath of Plates to remove balance of any fouling.

 CleanedPlates 100% visually inspected and DPI checked for cracks pin holes or materialfailure.

 RegasketPlates with OEM quality gaskets, Mechanical Bonding, Non-Hardening AdhesiveBonding, or Epoxy. 

 ThoroughQuality Inspection on Plates before packed/shipped. Complete Units are hydrotested prior to shipment.

 SequentialMarks on plates packs for easy handling and installation. 